H03/H05VVH2-F & H03/H05VV-F

Application

For use in connections of household appliances, plant and machinery, wiring purposes and for manufacturing cords.

Standard

BS EN 50525-2-11, DIN EN 50525-2-11; VDE 0285-525-2-11, EN 50525-2-11.

Technical Data

Nominal Voltage : 300/500V (H05VV-F & H05VVH2-F); 300/300V (H03VV-F & H03VVH2-F)
Insulation Resistance : Min. 20 GΩ x cm
Temperature Range : Flexing -5°C to +70°C. Fixed Installation : -30°C to +70°C
Minimum Bending Radius: Flexing 7.5 x cable ø; Fixed installation 4 x cable ø
Test Voltage : 4000V
Breakdown Voltage : Min. 8000V

Cable Construction

Bare copper, fine wire conductors, as per EN 60228 Cl.5. PVC core insulation TI2, to EN 50363-3.
Harmonised core colour to HD 308 (Refer Appendix Table No. 1-1). Cores stranded in layers with optimal lay-length.
PVC outer sheath TM2, to EN 50363-4.1.

H05VV-F is also available in oil resistant variant as H05VV5-F.
The outer sheath provided here is of special PVC, TM5 to BS EN 50363-4.1.

Properties

PVC self-extinguishing and flame retardant according to EN 60332-1-2.
Please complete the part numbers for these cables by adding the suffix (in place of “z”) for the sheath colour required:
1 – black (RAL 9005), 3 – grey (RAL 7001), 5 – white (RAL 9010). For Oil Resistant sheath kindly add “OR” after the part nos.